Evaluation of the Computer Fire Model DETACT-QS
ebook ∣ The Society of Fire Protection Engineers Series
By Society for Fire Protection Engineers

Sign up to save your library
With an OverDrive account, you can save your favorite libraries for at-a-glance information about availability. Find out more about OverDrive accounts.
Find this title in Libby, the library reading app by OverDrive.

Search for a digital library with this title
Title found at these libraries:
Loading... |
This engineering practice Guide, based on the DETACT-QS program, describes a model for predicting the response time of ceiling-mounted heat detectors/sprinklers and smoke detectors, installed under large unobstructed ceilings, for fires with user-defined, time-dependent heat release rate curves. The Guide provides information on the technical features, theoretical basis, assumptions, limitations, and sensitivities as well as guidance on the use of DETACT-QS. Evaluation is based on comparing predictions from DETACT-QS with results from full-scale fire experiments conducted in compartments with ceiling heights ranging from 2.44 m (8 ft) to 12.2 m (40 ft) and peak fire heat release rates ranging from 150 kW to 3.8 MW. Use of this model with building geometries or fire characteristics other than those used in this evaluation may require further evaluation or testing.